The flow sensor is the "ears" of the ET1 controller - it tells the controller that someone has turned on a tap. How it is installed determines how quickly and reliably the controller responds. Here are the rules from the user manual, gathered in one place.
1. Cold water supply
The sensor is installed on the cold water supply of the hot water appliance - a cylinder, combi boiler or heat exchanger - whose circulation the controller manages.
2. Shut-off valve, filter and non-return valve
Install a shut-off valve and a filter upstream of the sensor to protect it from dirt and damage, as well as a non-return valve.
3. Straight sections
There must be a straight pipe section of at least 5 DN before the sensor and at least 3 DN after it. Without this, the flow may be turbulent and the sensor will respond less reliably.
4. Flow direction
Install the body in line with the water flow direction and the markings on the body. Any position is fine - vertical, horizontal or in between.
5. Tight, but with care
The brass body has 2 tapered ¾" male threads. Seal them using any method that gives a tight joint, and use tools that will not damage the body. Make sure no sealant gets inside the sensor or the filter upstream of it - this is a common cause of slow controller response.
6. Electronics: dry and stress-free
Once the body is installed, fasten the electronic sensor with two M3 screws. The sensor must not be exposed to moisture, and the pipework must not put mechanical stress on it.
7. Cables, pump and power
5 cables come out of the bottom of the controller: 230 V power supply, 230 V circulation pump supply, flow sensor, circulation temperature sensor and current / limit temperature sensor. Connect the pump cable according to the pump manufacturer's instructions (the pump is not included in the set). Only then plug the controller into the mains. Always disconnect the 230 V supply before removing the fuse.
Installation should be carried out by a suitably qualified person, who confirms it with an entry in the warranty card.
Controller not detecting flow? Check this
- the installation direction of the flow sensor,
- whether the temperature sensors have been swapped,
- whether the filter before the flow sensor is blocked,
- the operation and capacity of the circulation pump,
- the non-return valve on the circulation branch (flow resistance),
- whether the circulation loop has been bled,
- the position of valves in the system and the water flow,
- the pressure in the hot water expansion vessel.